General specifications
| Product Name |
Eaton DS7 Soft starter
|
| Catalog Number |
134927
|
| Model Code |
DS7-342SX007N0-N
|
| EAN |
4015081317424
|
| Product Length/Depth |
94 mm
|
| Product Height |
130 mm
|
| Product Width |
45 mm
|
| Product Weight |
0.35 kg
|
| Certifications |
IEC/EN 60947-4-2
UL File No.: E251034 CSA C-Tick UkrSEPRO CE GB 14048.6 CSA File No.: 2511305 CSA Class No.: 321106 CSA-C22.2 No 0-M91 CSA-C22.2 No 14-05 UL 508 CSA22.2-14 UL |
| Global Catalog |
134927
|
| Product Type |
Soft starter
|
Product specifications
| Control voltage |
110/230 Vac control
|
| Phase |
Three-phase
|
| Special features |
Internal bypass
|
| Type |
Soft starter for three-phase loads
|
| Voltage rating |
110/230 V
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Internal bypass contacts
Internal bypass |
| Pollution degree |
2
|
| Class |
Other
|
| Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-30 |
| Connection to SmartWire-DT |
No
|
| Frame size |
FS1
|
| Altitude |
Max. 2000 m
Above 1000 m with 1 % derating per 100 m |
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature - min |
-5 °C
|
| Ambient storage temperature - max |
60 °C
|
| Ambient storage temperature - min |
-25 °C
|
| Assigned motor power at 200/208 V, 60 Hz, 3-phase |
2 HP
|
| Assigned motor power at 220/230 V, 60 Hz, 3-phase |
2 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 3-phase |
5 HP
|
| Equipment heat dissipation, current-dependent Pvid |
0.35 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Mains voltage - max |
480 V
|
| Mains voltage - min |
200 V
|
| Series |
Generation 7
|
| Output voltage |
110 - 230 V AC
|
| Number of outputs |
1 Relay Output (TOR)
|
| Screwdriver size |
PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver
0.6 x 5.5 mm/1 x 6 mm, Terminal screws, Control circuit cables |
| Voltage type |
AC
|
| Rated operational voltage (Ue) - min |
230 V
|
| Rated power three-phase motor, inline, at 230 V |
1.5 kW
|
| Rated power three-phase motor, inline, at 400 V |
3 kW
|
| Static heat dissipation, non-current-dependent Pvs |
0.35 W
|
| Voltage rating - max |
480 V
|
| Application |
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact
|
| Mounting position |
Vertical
|
| Input current |
4 mA (at 230 V AC, Digital inputs)
|
| Drop-out voltage |
AC operated: 0 - 15 V, AC operated
|
| Overvoltage category |
II
|
| Degree of protection |
IP20
NEMA 1 |
| Current consumption |
1.6 mA, Control circuit, Digital inputs, External 24 V
50 mA, Control circuit, Regulator supply |
| Functions |
Potential isolation between power and control sections
Single direction Min. ramp time 1 s - fast switching (semiconductor contactor) Suppression of closing transients Soft start function Suppression of DC components for motors |
| Delay time |
0 - 30 s, Soft start function, Ramp times
|
| Overload cycle |
AC-53a: 3 - 5: 75 - 10
|
| Drop-out time |
350 ms, Control circuit, Digital Inputs, AC operated
|
| Pick-up voltage |
108 - 253 V AC
|
| Radio interference class |
Class A (EN 55011)
|
| Pick-up time |
250 ms at AC
|
| Rated control voltage (Uc) |
110 - 230 V AC (-15 %/+10 %)
110 - 230 V AC |
| Supply frequency |
50/60 Hz, fLN, Main circuit
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
110 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
230 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
110 V
|
| Rated operational current (Ie) at AC-11 |
1 A
|
| Rated operational current (Ie) at AC-53 |
7 A
|
| Rated operational current for specified heat dissipation (In) |
7 A
|
| Rated operational power at 220/230 V, 50 Hz |
1.5 kW
|
| Rated operational power at 400 V, 50 Hz |
3 kW
|
| Rated operational voltage (Ue) - max |
480 V
|
| Vibration resistance |
2M2 to EN 60721-3-2
|
| Ramp/run-up time |
1 - 30 s
|
| Shock resistance |
8 g, 11 ms, Mechanical
|
| Suitable for |
Branch circuits, (UL/CSA)
|
| Tightening torque |
1.2 Nm, Screw terminals, Control circuit cables
1.2 Nm |
| Short-circuit protection rating |
3 x 170M1361, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths
PKM0-10 (+ CL-PKZ0), Type “1” coordination, Main conducting paths |
| Start voltage |
Max. 100 %, Soft start function, Start voltage = turn-off voltage
Min. 30 %, Soft start function, Start voltage = turn-off voltage |
| Terminal capacity (flexible with ferrule) |
2 x (0.75 - 2.5) mm², Main cables
1 x (0.75 - 2.5) mm², Main cables 2 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid) |
1 x (0.75 - 4) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 4) mm², Control circuit cables 2 x (0.75 - 2.5) mm², Main cables |
| Terminal capacity (solid/stranded AWG) |
18 - 10, Main cables
18 - 10, Control circuit cables |
Politica de retur