General specifications
| Product Name |
Eaton Moeller® series EMR6 Voltage monitoring relay
|
| Catalog Number |
184784
|
| EAN |
4015081788200
|
| Product Length/Depth |
103.7 mm
|
| Product Height |
85.6 mm
|
| Product Width |
22.5 mm
|
| Product Weight |
0.154 kg
|
| Certifications |
UL508
EAC RMRS CCC RCM CSA-C22.2 No. 14 GL |
| Model Code |
EMR6-VM600-A-1
|
Features & Functions
| Electric connection type |
Screw connection
|
| Functions |
Single-phase under voltage possible
DC-under voltage Single-phase over voltage possible DC-over voltage |
| Monitoring function |
Undervoltage
Overvoltage |
| Voltage measurement - min |
3 V
|
| Voltage measurement - max |
600 V
|
General
| Degree of protection |
Enclosure: IP50
Terminals: IP20 |
| Lifespan, mechanical |
30,000,000 Operations
|
| Mounting position |
As required
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Product Category |
EMR Measuring and monitoring relays
|
| Product Category |
EMR Measuring and monitoring relays
|
| Rated impulse withstand voltage (Uimp) |
4000 V AC
|
| Shock resistance |
Class 2
|
| LED indicator |
Status indication of energized output relay: Yellow LED
Status indication of Supply voltage: Yellow LED Status indication of errors: Red LED Other states depending on fault (see IL): Measured value Status indication of Supply voltage: Green, solid light |
| Type |
Voltage monitor
|
| Voltage type |
AC/DC
|
Climatic environmental conditions
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
60 °C
|
| Ambient storage temperature - min |
40 °C
|
| Ambient storage temperature - max |
85 °C
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
|
Electro magnetic compatibility
| Air discharge |
Air/contact discharge, according to IEC/EN 61000-4-2, level 3
|
| Burst impulse |
According to IEC/EN 61000-4-4, level 3
|
| Electromagnetic compatibility |
According to IEC/EN 60947-6-2
|
| Immunity to line-conducted interference |
Level 3 (according to IEC/EN 61000-4-6)
|
| Immunity to radiation |
Level 3 (according to IEC/EN 61000-4-3)
|
| Surge rating |
According to IEC/EN 61000-4-5 Level 4
|
Terminal capacities
| Connection type |
Snap fixing, top-hat rail IEC/EN 60715
|
| Terminal capacity (flexible with ferrule) |
2 x 0.5-1.5 mm²
|
| Terminal capacity (flexible with ferrule AWG) |
2 x 18-16
|
| Terminal capacity (solid) |
1 x 0.5-2.5 mm²
|
| Terminal capacity (solid AWG) |
18 - 14
|
| Screwdriver size |
5.5 x 0.8 mm, Terminal screw
|
| Tightening torque |
Min. 0.5 Nm, Screw terminals
0.8 Nm, Screw terminals |
Timing cycle
| Delay time |
Adjustable from 0.1 - 30 s, Response delay time
|
| Timing cycle |
Adjustable from 0.1 – 30 s, Reset delay/Off-delay time
|
Power supply
| Duty factor |
100 %, Power supply
|
| Power consumption |
2.6 VA
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
24 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
240 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
24 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
| Rated control supply voltage (Us) at DC - min |
24 V
|
| Rated control supply voltage (Us) at DC - max |
240 V
|
| Rated frequency - min |
50 Hz
|
| Rated frequency - max |
60 Hz
|
| Supply voltage |
24 - 240 V AC, 50/60 Hz
24 - 240 V DC |
| Voltage tolerance |
0.85 x Uc
1.1 x Uc |
Measuring circuits
| Hysteresis |
3 - 30 %
|
| Threshold value |
3 V AC, Min. undervoltage response value
3 V AC, Min. overvoltage response value 600 V AC, Max. undervoltage response value 600 V AC, Max. overvoltage response value |
Relay output contacts
| Number of contacts (change-over contacts) |
2
|
| Number of contacts (normally closed contacts) |
0
|
| Number of contacts (normally open contacts) |
0
|
| Lifespan, electrical |
100,000 Operation (at 230 V, AC-12, 4 A)
|