General specifications
| Product Name |
Eaton Moeller series xPole - AFDD+ Arc fault detection device
|
| Catalog Number |
187165
|
| Model Code |
AFDD-10/2/B/001-A
|
| EAN |
4015081822140
|
| Product Length/Depth |
80 mm
|
| Product Height |
73 mm
|
| Product Width |
52.5 mm
|
| Product Weight |
0.277 kg
|
| Compliances |
CE Marked
RoHS conform |
| Certifications |
CE
|
Delivery program
| Application |
Switchgear for residential and commercial applications
|
| Product range |
AFDD
|
| Basic function |
Arc fault circuit interrupter
|
| Product application |
Switchgear for residential and commercial applications
|
| Number of poles |
Two-pole
|
| Number of poles (protected) |
2
|
| Number of poles (total) |
2
|
| Release characteristic |
B
|
| Tripping characteristic |
B
|
| Rated current |
10 A
|
| Rated current of product range |
10-40 Ampere
|
| Fault current rating |
0.01 A
|
| Sensitivity type |
Pulse-current sensitive
Type A |
| Type |
AFDD+
|
Technical Data - Electrical
| Voltage rating |
230 V
|
| Rated impulse withstand voltage (Uimp) |
4
|
| Current test marks |
As per inscription
|
| Impulse withstand current |
Partly surge-proof, 250 A
|
| Frequency |
50 Hz
|
| Frequency rating |
50 Hz
|
| Leakage current type |
A
|
| Rated switching capacity (IEC/EN 61009) |
10 kA
|
| Rated short-circuit breaking capacity |
10 Kilo Ampere
|
| Rated short-circuit breaking capacity (EN 61009) |
10 kA
|
| Rated short-circuit breaking capacity (EN 61009-1) |
10 kA
|
| Test circuit AC |
170 - 264 Voltage AC
|
| Tripping |
Non-delayed
|
| Control voltage type auxiliary equipment |
AC
|
| Rated voltage auxiliary device |
230 V
|
| Pollution degree |
2
|
| Lifespan, electrical |
4000 operations
|
Technical Data - Mechanical
| Frame |
45 mm
|
| Width In Number Of Modular Spacings |
3
|
| Built-in width |
54 mm
|
| Device height |
80 mm
|
| Built-in depth |
67 mm
|
| Mounting style |
Tri-stable slide catch - enables removal from existing busbar combination
|
| Degree of protection |
IP20
|
| Degree of protection (built in) |
IP40
|
| Terminals (top and bottom) |
Twin-purpose
|
| Terminal protection |
Busbar tag shroud as per VBG4, ÖVE-EN 6
|
| Contact position indicator |
red / green
|
| Thickness of busbar material |
0.8 - 2 Square Millimeter
|
| Climatic proofing |
IEC/EN 61009
|
| Lifespan, mechanical |
20000 operations
|
Design verification as per IEC/EN 61439 - technical data
| Rated operational current for specified heat dissipation (In) |
10 A
|
| Equipment heat dissipation, current-dependent |
6 W
|
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature - min |
-25 °C
|
Design verification as per IEC/EN 61439
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
Additional information
| Current limiting class |
3
|
| Additional equipment attached at delivery |
Fire protection switch
|
| Types conform to |
IEC/EN 62606
IEC/EN 61009 |
Politica de retur
Transport
Putem livra practic prin curier la orice adresa din Romania. Rețineți că există restricții pentru unele produse, iar unele produse nu pot fi expediate către destinații internaționale.