Standards
IEC, UL, CSA, CCC, GL
Lifespan, mechanical [Operations]
30 x 106
Climatic proofing
Damp heat, cyclical to IEC 60068-2-30: 24 h cycle, 55° C, 93% relative humidity, 96 h
Ambient temperatureOperationOperating ambient temperature min.
-25 °C
Ambient temperatureOperationOperating ambient temperature max.
+60 °C
Ambient temperatureStorage
- 40 - 85 °C
Mounting position
As required
Degree of protectionTerminals
IP20
Degree of protectionEnclosures
IP50
Terminal capacitiesSolid
1 x 0.5-2.5 (1 x 18-14 AWG) mm2
Terminal capacitiesFlexible with ferrule
2 x 0.5-1.5 (2 x 18-16 AWG) mm2
Standard screwdriver
5.5 x 0.8 mm
Tightening torque
0.6 - 0.8 Nm
Fixing
Snap fixing, top-hat rail IEC/EN 60715
MTBF (mean time between failures)
382977 h
Rated impulse withstand voltage [Uimp]
4000 V AC
Overvoltage category/pollution degree
III/3
Supply voltage
160 - 300 V AC, 50/60 Hz
Voltage tolerance
0.85 - 1.1 x Uc
Rated frequency [f]
50 - 60 Hz
Response delay time
0.2 s
Reset delay/Off-delay time
Adjustable from 0.1 – 30 s
Time error within supply voltage
0.5 %
Time error within temperature range
0.06 %/°C
Frequency
50/60 ± 10 % Hz
Frequency
50/60 ± 10 % Hz
Temperature error
0.06 %/°C
Error within supply voltage
0.5 %
Supply voltage
LED green: R on
Output relay energized
LED green: R flashes
Overvoltage
LED red: F1 on
Undervoltage
LED red: F2 on
Phase failure
LED red: F1 on, F2 flashes
Phase sequence error
LED red: F1, F2 flashing
Status indicator (LED)
Green, solid: Supply voltage
Yellow, solid: Relay energized
Yellow, flashing: Delay time running
Red, solid (F1 & F2): Imbalance
Red, solid (F1): Overvoltage
Red, solid (F2): Undervoltage
Red: F1 solid, F2 flashing: Phase failure
Red, flashing (F1 & F2 alternating): Phase sequence fault
Rated operational voltage [Ue ]
250 V AC
Rated operational current [Ie ]AC-12 at 230 V [Ie ]
4 A
Rated operational current [Ie ]AC-15 with 230 V [Ie]
3 A
Rated operational current [Ie ]DC-12 at 24 V [Ie ]
4 A
Rated operational current [Ie ]DC-13 at 24 V [Ie ]
2 A
Minimum Switching capacity
10 mA / 24 V
Lifespan, electrical (AC-12/230 V/4 A) [Operations]Lifespan, electrical [Operations]
0.1 x 106
Short-circuit ratingmax. fuse [Fast/gL]
5 A
Electromagnetic compatibility (EMC)
Electromagnetic compatibility
IEC/EN 60947-6-2
ESD [Air/contact discharge]
IEC/EN 61000-4-2 level 3 kV
HF-immunity to radiation
IEC/EN 61000-4-3 level 3
Burst
IEC/EN 61000-4-4 level 3
Surge
IEC/EN 61000-4-5 Level 4
HF-immunity to line-conducted interference
IEC/EN 61000-4-6 level 3
feedback Reclama un comentariu