Thermostat Power Requirements 7 Vdc, 2.4 W min. (from VC3000) Operating Conditions 0 to 50 °C (32 to 122 °F); 0 to 95% RH non-condensing Storage Conditions -30 to 50 °C (-22 to 122 °F); 0 to 95% RH non-condensing Temperature Sensor Local 10k NTC type 2 thermistor Temp. Sensor Resolution ± 0.1 °C (± 0.2 °F) Temp. Control Accuracy ±0.5 °C (±0.9 °F ) @ 21 °C (70 °F) typical calibrated Humidity Sensor and Calibration Single point calibrated bulk polymer sensor Humidity Sensor Precision Reading range from 10 to 90% RH noncondensing 10 to 20% precision is 10%; 20 to 80% precision is 5%; 80 to 90% precision is 10%
Humidity Sensor Stability <1.0% annual drift (typical) Dehumidification Setpoint Range 30 to 95% RH Occupied and Unoccupied Setpoint Range Cooling 12 to 38 °C (54 to 100 °F) Occupied and Unoccupied Setpoint Range Heating 5 to 32 °C (40 to 90 °F) Room and Outdoor Air Temperature Display -40 to 50 °C (-40 to 122 °F) Proportional Band for Room Temperature Range Control Cooling & Heating: 1.8 °C (3.2 °F ) Binary Inputs Dry contact across terminal BI1, BI2 & UI3 to Scom Economizer Analog Output Rating 0 to 10 Vdc into 2k Ω resistance min. Economizer Analog Output Accuracy ±3% typical Wire Gauge 18 gauge maximum, 22 gauge recommended WARRANTY Limited Warranty 18 months