Dimensions (W x H x D)
107.5 x 90 x 72 without/79 with adapter for MCC (6 SU) mm
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using 3 fixing brackets ZB4-101-GF1 (accessories)
Solid
0.2/4 (AWG 22 - 12) mm2
Flexible with ferrule
0.2/2.5 (AWG 22 - 12) mm2
Standard screwdriver
0.8 x 3.5 mm
Max. tightening torque
0.6 Nm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
LCD display (clearly legible)
0 - 55 °C
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Air pressure (operation)
1080 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
II/2
Electrostatic discharge (ESD)applied standard
IEC/EN 61000-4-2, Level 3
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst
IEC/EN 61000-4-4, level 3 kV
power pulses (Surge)
2 kV (supply cables, symmetrical, EASY...AC)
0.5 kV (supply cables, symmetrical, easy-DC)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Back-up of real-time clock
Back-up of real-time clock
① Backup time (hours) with fully charged double layer capacitor
② Service life (years)
Accuracy of the real-time clock
part no. ± 5 (± 0.5 h⁄Year) s/day
Write cycles of the retentive memory
10000000000 (10¹⁰) (Read-write cycles)
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Input current
normally 140 mA at Ue
Voltage dips
≤ 10
(IEC/EN 61131-2) ms
Heat dissipation [P]
Normally 3.4 W
MemoryProgram code/data
256/14 segments of 16 KB each kByte
MemoryMarker/retentive data
16/4/4/8 KByte
Cycle time for 1 k of instructions (Bit, Byte)
< 0.3 ms
PRG interface RS232Data transfer rate
4.8, 9.6, 19.2, 38.4, 57.6, 115.2 (character format: 8 bit data, no parity, 1 stop bit) kBit/s
PRG interface RS232Connection types
RJ45-bus
PRG interface RS232Potential isolation
none
PRG interface RS232Master modeData transfer rate
0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 kbit/s
PRG interface RS232Master modeCharacter formats
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1
PRG interface RS232Master modeNumber of transmission bytes in a block
190 bytes
PRG interface RS232Master modeNumber of received bytes in a block
190 bytes
EthernetData transfer rate
10 MBit/s, 100 m Mbit/s
EthernetConnection types
RJ45
EthernetPotential isolation
No
CANopen®Data transfer rate
500 kBit/s, 25 m 250 kBit/s, 60m 125 kBit/s, 125 m 50 kBit/s, 300 m 20 kBit/s, 700 m 10 kBit/s, 1000 m
CANopen®Bus termination (first and last station)
EASY-NT-R plug (incl. bus terminating resistor 120 Ω)
CANopen®Connection types
2 x RJ45, 8 pole
Mode slaveStations
max. 126 Number
Mode slavePDO type
Asynchronous, cyclic, acyclic
Mode slaveControl contact rated current
To DS 301 V4
Inputs can be used as analog inputs
4 (I7, I8, I11, I12)
Status Display
LCD-Display
Potential isolation
from the outputs: yes
to network easyNet, easyLink
Rated operational voltage [Ue]
24 V DC
Input voltage
< 5 (I1 - I6, I9 - I10) < 8 (I7, I8, I11, I12) at signal "0"
> 15.0 (I1 - I6, I9, I10) > 8.0 (I7, I8, I11, I12) at signal "1" V DC
Input current on 1 signalInput current at signal 1
3.3 (I1 to I6)
2.2 (I7, I8)
3.3 (I9, I10)
2.2 (I11, I12) mA
Deceleration time
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1")
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1") ms
Cable length
100 (unshielded) m
Incremental counterNumber of counter inputs
1 (I1, I2, I3, I4)
Incremental counterValue range
32 Bit
Incremental counterCounter frequency
≦ 40 kHz
Incremental counterPulse shape
Square
Incremental counterCounter inputs
I1, I2
Incremental counterReference input
I3
Incremental counterInput for reference switch
I4
Incremental counterCounter inputs I1 and I2, I3 and I4
1
Incremental counterSignal offset
90°
Rapid counter inputsNumber
2 (I1, I2) at 16 Bit or 1 (I1) at 32 Bit
Rapid counter inputsValue range
16/32 Bit
Rapid counter inputsCable length
≦ 20 (screened) m
Rapid counter inputsCounter frequency
≦ 50 kHz
Rapid counter inputsPulse shape
Square
Number
4 (I7, I8, I11, I12)
Potential isolation
from the outputs: yes
to interface/memory card: no
Resolution
0.01 V analog
0.01 V digital
10 Bit (value 0 - 1023)
Accuracy of actual valueWithin a single device
± 2, (I7, I8, I11, I12) ± 0.12 V %
Conversion time, analog/digital
each CPU cycle ms
Cable length
≦ 30, screened m
Max. output current
0.01 A
Overload and short-circuit protection
Yes
Resolution
0.01 V DC analog
10 Bit (value 0 - 1023) digital
Accuracy-25 °C - 55 °C
2 %
Conversion time, analog/digital
each CPU cycle ms
Parallel switching of outputs for increased output
Not permissible
Protection of an output relay
Miniature circuit-breaker B16 or fuse 8 A (slow)
Potential isolation
from power supply: yes
From the inputs: yes
in groups
Safe isolation according to EN 50178: 300 V AC
Basic isolation: 600 V AC
Lifespan, mechanical [Operations]
10 x 106
ContactsConventional thermal current (10 A UL)
8 A
ContactsRecommended for load: 12 V AC/DC
> 500 mA
ContactsShort-circuit-proof cos ϕ = 1, characteristic B16 at 600 A
16 A
ContactsShort-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A
16 A
ContactsRated impulse withstand voltage Uimp of contact coil
6 kV
ContactsRated operational voltage [Ue]
250 V AC
Rated insulation voltage [Ui]
250 V AC
Safe isolation according to EN 50178
300 between coil and contact
300 between two contacts V AC
Making capacityAC–-15, 250 V AC, 3 A (600 ops./h) [Operations]
300000
Making capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations]
200000
Breaking capacityAC-15, 250 V AC, 3 A (600 Ops./h) [Operations]
300000
Breaking capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations]
200000
Filament bulb load1000 W at 230/240 V AC [Operations]
25000
Filament bulb load500 W at 115/120 V AC [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACWith upstream electrical device [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACUncompensated [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated [Operations]
25000
Switching frequencyMechanical operations
10 x 106
Switching frequencySwitching frequency
10 Hz
Switching frequencyResistive load/lamp load
2 Hz
Switching frequencyInductive load
0.5 Hz
UL/CSAUninterrupted current at 240 V AC
10 A
UL/CSAUninterrupted current at 24 V DC
8 A
UL/CSAACControl Circuit Rating Codes (utilization category)
B 300 Light Pilot Duty
UL/CSAACMax. rated operational voltage
300 V AC
UL/CSAACmax. thermal continuous current cos ϕ = 1 at B 300
5 A
UL/CSAACmax. make/break cos ϕ ≠ capacity 1 at B 300
3600/360 VA
UL/CSADCControl Circuit Rating Codes (utilization category)
R 300 Light Pilot Duty
UL/CSADCMax. rated operational voltage
300 V DC
UL/CSADCMax. thermal uninterrupted current at R 300
1 A
UL/CSADCMax. make/break capacity at R 300
28/28 VA
Bus termination (first and last station)
EASY-NT-R plug (incl. bus terminating resistor 120 Ω)