Standards
EN 61000-6-2
EN 61000-6-3
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-30
IEC/EN 61131-2
EN 61010
EN 50178
Approvalsshipping classification
DNV GL
Dimensions (W x H x D)
71.5 x 90 x 58 mm
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Connection type
screw terminal
Screw terminalsSolid
0.2 - 4 mm2
Screw terminalsflexible
0.2 - 2.5 mm2
Screw terminalsSolid or flexible conductor, with ferrule
0,2 - 2,5 mm2
Screw terminalsSolid or stranded
22 - 12 AWG
Screw terminalsStandard screwdriver
0.8 x 3.5 mm
Screw terminalsTightening torque
0.5 - 0.7 Nm
Screw terminalsStripping length
6.5 mm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
relative humidity
in accordance with IEC 60068-2-30, IEC 60068-2-78
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations
In accordance with IEC 60068-2-6
constant amplitude 0.15 mm: 10 - 57
constant acceleration 2 g: 57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
0.3 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
III/2
Electrostatic discharge (ESD)applied standard
nach IEC/EN 61000-4-2
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
0.08 - 1.0 GHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1 V/m
Radio interference suppression
EN 61000-6-3 Class B
Burst
according to IEC/EN 61000-4-4
Supply cables: 2
Signal cables: 2 kV
power pulses (Surge)
according to IEC/EN 61000-4-5
1 kV (supply cables, symmetrical)
2 kV (supply cables, asymmetrical)
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
nach EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Insulation resistance
in accordance with EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Rated operational voltage [Ue]
12/24 DC (-15/+20%)
24 AC (-15/+10%) V
Permissible range [Ue]
10.2 - 28.8 V DC
20.4 - 26.4 V AC
Protection against polarity reversal
yes
Frequency
50/60 (± 5%) Hz
Input current
max. 200 mA at 12 V DC
max. 125 mA at 24 V DC
Voltage dips
≤ 20 ms at 24 V AC
10 ms at 24 V DC
1 ms at 12 V DC ms
Heat dissipation at 24 V DC
3 W
Potential isolation
from power supply: no
between inputs: no
from the outputs: yes
to base unit: yes
to expansion devices: yes
Rated operational voltage [Ue]
12 V DC
Input voltage
Condition 0: ≦ 5 (I1 - I8)
Condition 1: ≧ 8 (I1 - I8) V DC
Input current at signal 1
1.75 mA (I1 - I8) mA
Deceleration time
type 0.2 (0 -> 1)
type 0.15 (1 -> 0) ms
Cable length
100 (unshielded) m
Potential isolation
from power supply: no
between inputs: no
from the outputs: yes
to base unit: yes
to expansion devices: yes
Rated operational voltage [Ue]
24 V DC
Input voltage
Signal 0: ≦ 5 (I1 - I8)
Condition 1: ≧ 15 (I1 - I8) V DC
Input current at signal 1
3.3 (I5 - I8) mA
Deceleration time
type 0.1 (0 -> 1)
type 0.2 (1 -> 0) ms
Cable length
100 (unshielded) m
Potential isolation
from power supply: no
between inputs: no
from the outputs: yes
to base unit: yes
to expansion devices: yes
Rated operational voltage [Ue]
24 V AC
Input voltage (AC = sinusoidal) [Ue]
Status 0: ≦ 5 (I1 - I8)
Condition 1: ≧ 14 (I1 - I8) V
Input current at signal 1
I5 - I8: 3.5 (at 24 VAC/DC) mA
Deceleration time
type 25⁄21 (0 - > 1/1 -> 0, 50/60Hz) ms
Cable length
40 (unshielded) m
Parallel switching of outputs for increased output
Not permitted
Protection of an output relay
B16 circuit breaker or 8 A (T) fuse
Potential isolation
Safe isolation according to EN 50178: 300 V AC
Basic isolation: 600 V AC
from power supply: yes
From the inputs: yes
between outputs: yes
to expansion devices: yes
ContactsConventional thermal current (10 A UL)
5 A
ContactsRecommended for load: 12 V AC/DC
> 500 mA
ContactsRated impulse withstand voltage Uimp of contact coil
6 kV
ContactsRated operational voltage [Ue]
240 V AC
Rated insulation voltage [Ui]
240 V AC
Safe isolation according to EN 50178
300 between coil and contact
300 between two contacts V AC
Making capacityAC–-15, 250 V AC, 3 A (600 ops./h) [Operations]
300000
Making capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations]
200000
Breaking capacityAC-15, 250 V AC, 3 A (600 Ops./h) [Operations]
300000
Breaking capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations]
200000
Filament bulb load1000 W at 230/240 V AC [Operations]
25000
Filament bulb load500 W at 115/120 V AC [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACWith upstream electrical device [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACUncompensated [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated [Operations]
25000
Switching frequencyMechanical operations
10 x 106
Switching frequencySwitching frequency
10 Hz
Switching frequencyResistive load/lamp load
2 Hz
Switching frequencyInductive load
0.5 Hz
UL/CSAUninterrupted current at 240 V AC
5 A
UL/CSAUninterrupted current at 24 V DC
5 A
UL/CSAACControl Circuit Rating Codes (utilization category)
B 300 Light Pilot Duty
UL/CSAACMax. rated operational voltage
300 V AC
UL/CSAACmax. thermal continuous current cos ϕ = 1 at B 300
5 A
UL/CSAACmax. make/break cos ϕ ≠ capacity 1 at B 300
3600/360 VA
UL/CSADCControl Circuit Rating Codes (utilization category)
R 300 Light Pilot Duty
UL/CSADCMax. rated operational voltage
300 V DC
UL/CSADCMax. thermal uninterrupted current at R 300
1 A
UL/CSADCMax. make/break capacity at R 300
28/28 VA