Standards
EN 61000-6-2
EN 61000-6-3
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-30
IEC/EN 61131-2
EN 61010
EN 50178
Approvalsshipping classification
DNV GL
Dimensions (W x H x D)
35.5 x 90 x 58 mm
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Connection type
screw terminal
Screw terminalsSolid
0.2 - 4 mm2
Screw terminalsflexible
0.2 - 2.5 mm2
Screw terminalsSolid or flexible conductor, with ferrule
0,2 - 2,5 mm2
Screw terminalsSolid or stranded
22 - 12 AWG
Screw terminalsStandard screwdriver
0.8 x 3.5 mm
Screw terminalsTightening torque
0.5 - 0.7 Nm
Screw terminalsStripping length
6.5 mm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
relative humidity
in accordance with IEC 60068-2-30, IEC 60068-2-78
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations
In accordance with IEC 60068-2-6
constant amplitude 0.15 mm: 10 - 57
constant acceleration 2 g: 57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
0.3 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
III/2
Electrostatic discharge (ESD)applied standard
nach IEC/EN 61000-4-2
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
0.08 - 1.0 GHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1 V/m
Radio interference suppression
EN 61000-6-3 Class B
Burst
according to IEC/EN 61000-4-4
Supply cables: 2
Signal cables: 2 kV
power pulses (Surge)
according to IEC/EN 61000-4-5
0.5 kV (supply cables, symmetrical)
1 kV (supply cables, asymmetrical)
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
nach EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Insulation resistance
in accordance with EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Protection against polarity reversal
yes
Input current
max. 40 mA at Ue
Heat dissipation at 24 V DC
1 W
Potential isolation
from power supply: no
between inputs: no
from the outputs: no
to expansion devices: yes
to base unit: yes
Rated operational voltage [Ue]
24 V DC
Input voltage
Signal 0: ≦ 5 (I1 - I4)
Signal 1: ≧ 15 (I1 - I4) V DC
Input current at signal 1
3.3 (I1 – I4) mA
Deceleration time
type 0.1 (0 -> 1)
type 0.2 (1 -> 0) ms
Cable length
100 (unshielded) m
Rated operational voltage [Ue]
24 V DC
Permissible range [Ue]
20.4 - 28.8 V DC
Protection against polarity reversal
Yes (Caution: A short circuit will occur if a supply voltage of the wrong polarity is applied to the outputs.)
Potential isolation
from power supply: no
between the inputs: no
to the outputs: no
to base unit: yes
to expansion devices: yes
Rated operational current at signal „1” DC per channel [Ie]
Max. 0.5 A
Residual current on 0 signal per channel
< 0.005 mA
Max. output voltage
1 (at status 0 per channel)
U = Ue - 1 V (signal 1 at Ie = 0.5 A) V
Short-circuit protection
yes, electronic (Q1 - Q4)
Short-circuit tripping current for Ra ≦ 10 mΩ
0.7 ≦ Ie ≦ 1.7 per output
depending on number of active channels and their load A
Total short-circuit current
6.8 A
Max. operating frequency with constant resistive load
abhängig von der Zykluszeit des Basisgeräts und bei Erweiterungsgeräten auch von deren Übertragungszeit Operations/h
Parallel connection of outputsWith resistive load, inductive load with external suppressor circuit, combination within a group
Group 1: Q1 to Q4
Parallel connection of outputsNumber of outputs [max.]
4
Parallel connection of outputsMax. total current
2 A
Inductive load to EN 60947-5-1Without external suppressor circuitDC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 HUtilization factor
0.25 g
Inductive load to EN 60947-5-1Without external suppressor circuitDC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 HDuty factor
100 % DF
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 15 ms, R = 48 Ω, L = 0.24 HUtilization factor
0.25 g
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 15 ms, R = 48 Ω, L = 0.24 HDuty factor
100 % DF
Inductive load to EN 60947-5-1With external suppressor circuitUtilization factor
1 g
Inductive load to EN 60947-5-1With external suppressor circuitDuty factor
100 % DF
Inductive load to EN 60947-5-1With external suppressor circuitMax. switching frequency, max. duty factor
Depending on the suppressor circuit Operations