Standards
EN 61000-6-2
EN 61000-6-3
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-30
IEC/EN 61131-2
EN 61010
EN 50178
Approvalsshipping classification
DNV GL
Dimensions (W x H x D)
35.5 x 90 x 58 mm
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Connection type
Push-in terminals
Push-in terminalsSolid
0.2 - 2.5 mm2
Push-in terminalsflexible
0.2 - 2.5 mm2
Push-in terminalsSolid or flexible conductor, with ferrule
0,25 - 1,5 mm2
Push-in terminalsSolid or stranded
24 - 14 AWG
Push-in terminalsStandard screwdriver
0.4 x 2.5 mm
Push-in terminalsStripping length
8 mm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
relative humidity
in accordance with IEC 60068-2-30, IEC 60068-2-78
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations
In accordance with IEC 60068-2-6
constant amplitude 0.15 mm: 10 - 57
constant acceleration 2 g: 57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
0.3 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
III/2
Electrostatic discharge (ESD)applied standard
nach IEC/EN 61000-4-2
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
0.08 - 1.0 GHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1 V/m
Radio interference suppression
EN 61000-6-3 Class B
Burst
according to IEC/EN 61000-4-4
Supply cables: 2
Signal cables: 2 kV
power pulses (Surge)
according to IEC/EN 61000-4-5
0.5 kV (supply cables, symmetrical)
1 kV (supply cables, asymmetrical)
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
nach EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Insulation resistance
in accordance with EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Protection against polarity reversal
yes
Input current
max. 40 mA at Ue
Power loss [P]
Normally 1 W
Heat dissipation at 24 V DC
1 W
Analog inputs temperature resistance Pt100 or Ni1000 sensors
Input type resistance sensor
Platinum sensor Pt100, platinum sensor Pt1000, nickel sensor Ni1000
Temperature range
Pt100, Pt1000: -100 - +200 (-148 - +392)
Pt100, Pt1000: -100 - +400 (-148 - +752)
Pt100, Pt1000: -100 - +800 (-148 - +1472)
Ni1000: -50 - +100 (-58..+212)
Ni1000: -50 - +250 (-58..+482) °C, (°F)
Potential isolation
from power supply: no
to the inputs: no
to the expansion units: yes
Resolution digital, scaling per sensor
12 Bit (0- 4095)
Measuring principle
Two or three wire per sensor, selectable by connection of sensor
Accuracy (without electromagnetic compatibility interference)
1 %
Conversion time, analog/digital
250, 1000, 2500, 10000 ms
Diagnostics
Card diagnostic: yes
below lower measurement range: yes
Upper sensor measuring range exceeded: yes
Cable length
≦ 30, unshielded m