Product name
Eaton Moeller® series EASY I/O expansion
Product Length/Depth
58 millimetre
Product height
90 millimetre
Product width
36 millimetre
Product weight
0.1 kilogram
Compliances
Contact Manufacturer
Certifications
EN 50178
IEC/EN 61000-4-2
IEC 60068-2-6
EN 61010
CULus per UL 61010
IEC/EN 61000-6-2
IEC 60068-2-27
IEC 60068-2-30
IEC/EN 61131-2
CSA-C22.2 No. 61010
IEC/EN 61000-6-3
UL Listed
UL File No.: E205091
CE
DNV GL
UL Category Control No.: NRAQ, NRAQ7
UL hazardous location group D (propane)
UL hazardous location group B (hydrogen)
UL hazardous location group A (acetylene)
UL hazardous location division 2
UL hazardous location group C (ethylene)
UL hazardous location class I
Product Type
I/O expansion
Features
Expandable
Expansion device
Degree of protection
IP20
Insulation resistance
According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Mounting method
Front build in possible
Rail mounting possible
Wall mounting/direct mounting
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Product category
Control relays easyE4
Resolution
12 Bit (value 0 - 4095, Analog inputs)
12 Bit (value 0 - 4095, Analog outputs)
Software
EASYSOFT-SWLIC/easySoft7
Ambient conditions, mechanical
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
Horizontal
Vertical
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
57 - 150 Hz, 2 g constant acceleration
10 - 57 Hz, 0.15 mm constant amplitude
According to IEC/EN 60068-2-6
Climatic environmental conditions
Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Environmental conditions
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Condensation: prevent with appropriate measures
Relative humidity
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
Electro magnetic compatibility
Burst impulse
According to IEC/EN 61000-4-4
2 kV, Supply cable
2 kV, Signal cable
Electromagnetic fields
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 61000-6-3)
Surge rating
0.5 kV, Supply cables, symmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
1 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
Voltage dips
20 ms
≤ 10 ms, Bridging voltage dips
Terminal capacity
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
0.2 - 4 mm² (AWG 22 - 12), solid
Screwdriver size
3.5 x 0.8 mm, Terminal screw
Tightening torque
0.6 Nm, Screw terminals
Heat dissipation
3.4 W (at 24 V DC)
Inrush current
12.5 A (for 6 ms)
Rated operational voltage
20.4 - 28.8 V DC
24 V DC (-15 %/+ 20 % - power supply)
Supply voltage at AC, 50 Hz - min
0 V AC
Supply voltage at AC, 50 Hz - max
0 V AC
Supply voltage at DC - min
20.4 V DC
Supply voltage at DC - max
28.8 V DC
Short-circuit protection
≥ 1A (T), Fuse, Power supply
Connection type
Screw terminal
Cable length
≤ 30 m, screened, Analog outputs
≤ 30 m, screened, Analog inputs
10 m, screened, Analog inputs
Accuracy
1 %, Analog inputs at -25 °C - 55 °C
Number of inputs (analog)
4
Number of inputs (digital)
0
Number of outputs (analog)
2
Number of outputs (digital)
0
Signal range
4 - 20 mA, Analog outputs
0 - 20 mA, Analog inputs
0 - 10 V DC, Analog inputs
0 - 10 V DC, Analog outputs
4 - 20 mA, Analog inputs
0 - 20 mA, Analog outputs
Explosion safety category for gas
None
Potential isolation
Between Analog inputs and Power supply: no
Between Analog inputs and Inputs/Outputs: no
Between Analog outputs and Inputs/Outputs: no
Between Analog inputs and expansion devices: yes
Between Analog outputs and Power supply: no
Between Analog outputs and expansion devices: no
Protection against polarity reversal
Yes, for supply voltage (Siemens MPI optional)
Explosion safety category for dust
None
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
2.5 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
feedback Reclama un comentariu