Description
primary chopper
controlled
Phases
Single-phase
Input voltage range
85 - 264 V AC
Nominal input voltage
100 - 240 V AC
Rated output voltage
24 V DC (± 3%)
Rated output current
1.25 A
For use with
easy500
easy700
easy800
MFD-CP8
EC4P
ES4P
easyE4
Description

for DMI module

TECHNICAL DATA

General
Standards
EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
71.5 (4 PE) x 90 x 58 mm
Weight
0.25 kg
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Terminal capacities
Solid
0.2/4 (AWG 22 - 12) mm2
Flexible with ferrule
0.2/2.5 (AWG 22 - 12) mm2
Standard screwdriver
0.8 x 3.5 mm
Max. tightening torque
0.6 Nm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
Storage
- 40 - 70 °C
Relative humidity, non-condensing (IEC/EN 60068-2-30)Air humidity, non-condensing, min.
5 %
Relative humidity, non-condensing (IEC/EN 60068-2-30)Air humidity, non-condensing, max.
95 %
Air pressure (operation)
795 - 1080 hPa
Max. installation altitude above sea level, observe derating with higher altitudes
2000 m
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Air discharge
8 kV
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst pulses (IEC/EN 61000-4-4, level 3)
2 kV
Power pulses (surge) (IEC/EN 61000-4-5)
2 (supply cables, symmetrical) kV
High-energy pulses (surge) (IEC/EN 61000-4-5, level 2), 24 V
0.5 (outgoer cables symmetrical, EASY…DC) kV
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Surge voltage (EN 50178), 24 V
6 kV
Insulation resistance
Clearance in air and creepage distances
EN 50178
Insulation resistance
EN 50178
Protection class Uout to Uin
Class II to IEC 60536
Potential isolation primary/secondary
Yes, SELV (VDE 0100 Part 410; IEC 60364-4-41, HD 384.4.41 S2) EN 60950, EN 50178
Input voltage
Rated voltage
100/120/230/240 (-15/+10 %) V
Protective switches AC
FAZ-C2/1 or FAZ-B6/1
Voltage range
85 - 264 V AC
Frequency range
47 - 63 Hz
Mains failure bridging 115/230 V (IEC/EN 61000-4-11)
> 20/> 40 ms
Fuse 115/230 V
2/1 slow A
Rating data
Efficiency
> 83 %
Power consumption
Normally 35 W
Power loss [P]
Normally 5 W
Input current
Input current nominal 115/240 V
Approx. 0.6/0.3 A
Inrush current at 25 °C 230 V
< 18 A
Output voltage
24 V DCRated value
24 V DC
24 V DCTolerance
± 3 %
24 V DCSwitching peaks 115/230
< 5 mVPP
24 V DCEffect of input voltage
± 1 %
24 V DCEffect with 25 - 100 % load change
± 2 %
24 V DCCan be connected in parallel to increase power
Yes
Output current
24 V DCOutput current
0 - 1.25 A
24 V DCEffectiveness of current limitation
> 1.5 A
24 V DCReduction of output voltage after current limitation
< 18 V
24 V DCOverload proof
Yes, by current limitation
24 V DCProof against sustained short circuit
Yes, hickup mode, approx. 2 Hz
Special load conditions
Lamp load, cold, 24 V DC
10 W
Base load present
5 W
Behaviour on emergency-stop in 24 V circuit, disconnection with contactor (contactor load, no damage)
30 W
Displays
Indication of output voltage (LED, continuous green light = OK)
24 V DC

DESIGN VERIFICATION AS PER IEC/EN 61439

Technical data for design verification
Static heat dissipation, non-current-dependent [Pvs]
5 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

TECHNICAL DATA ETIM 8.0

Programmable logic controllers PLC (EG000024) / PLC system power supply (EC000599)
Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / SPS system power supply (ecl@ss10.0.1-27-24-22-09 [AKE532014])
Input voltage at AC 50 Hz
85 - 264 V
Input voltage at AC 60 Hz
85 - 264 V
Input voltage at DC
0 - 0 V
Type of voltage (input voltage)
AC
Max. input current AC 50 Hz
0.6 A
Max. input current AC 60 Hz
0.6 A
Max. input current DC
0 A
Type of output voltage
AC
Output voltage at AC 50 Hz
0 - 18 V
Output voltage at AC 60 Hz
0 - 0 V
Output voltage at DC
0 - 24 V
Max. output current AC 50 Hz
1.25 A
Max. output current AC 60 Hz
0 A
Max. output current DC
1.25 A
Power output
30 W
Redundancy
No
Suitable for safety functions
No
Width
72 mm
Height
90 mm
Depth
58 mm

DIMENSIONS

252X008
252X003
EATON
212319

Politica de retur

 Puteți returna majoritatea articolelor noi, nedeschise în termen de 14 de zile de la livrare, pentru o rambursare completă. Vom plăti, de asemenea, costurile de transport pentru retur dacă returnarea este rezultatul unei erori noastre (ați primit un articol incorect sau defect etc.).

 Ar trebui să vă așteptați să primiți rambursarea în termen de doua săptămâni de la livrarea pachetului expeditorului returnat, cu toate acestea, în multe cazuri, veți primi o rambursare mai rapid. Această perioadă de timp include timpul de tranzit pentru a primi returnarea dvs. de la expeditor (5 până la 10 zile lucrătoare), timpul necesar pentru procesarea returnării dvs. după ce îl primim (3 până la 5 zile lucrătoare) și timpul necesar banca dvs. pentru a procesa cererea noastră de rambursare (5 până la 10 zile lucrătoare).

 Dacă trebuie să returnați un articol, pur și simplu conectați-vă la contul dvs., vizualizați comanda utilizând link-ul „Finalizare comenzi” din meniul Contul meu și faceți clic pe butonul Returnați articolele. Vă vom anunța prin e-mail cu privire la rambursarea dvs. după ce am primit și procesat articolul returnat.

 

Transport

 

Putem livra practic prin curier la orice adresa din Romania. Rețineți că există restricții pentru unele produse, iar unele produse nu pot fi expediate către destinații internaționale.

 Când plasați o comandă, vom estima datele de expediere și livrare pentru dvs. în funcție de disponibilitatea articolelor dvs. și de opțiunile de livrare pe care le alegeți. În funcție de furnizorul de transport pe care îl alegeți, este posibil ca estimările datei de expediere să apară pe pagina de oferte de livrare.

chat Comentarii (0)