Standards
IEC/EN 60947, VDE 0660, UL, CSA
Component lifespanat Ue = 230 V, AC-15, 3 A [Operations]
1.3 x 106
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +60 °C
Ambient temperatureEnclosed
- 25 - 40 °C
Ambient temperatureAmbient temperature, storage
- 40 - 80 °C
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msBasic unit with auxiliary contact moduleN/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msBasic unit with auxiliary contact moduleN/C contact
5 g
Degree of Protection
IP20
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Terminal capacitiesScrew terminalsSolid
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacitiesScrew terminalsFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacitiesScrew terminalsSolid or stranded
18 – 14 AWG
Terminal capacitiesScrew terminalsPozidriv screwdriver
2 Size
Terminal capacitiesScrew terminalsStandard screwdriver
0.8 x 5.5
1 x 6 mm
Terminal capacitiesScrew terminalsMax. tightening torque
1.2 Nm
Interlocked opposing contacts within an auxiliary contact module (to IEC 60947-5-1 Annex L)
Yes
N/C contact (not late-break contact) suitable as a mirror contact (to IEC/EN 60947-4-1 Annex F)
DILM7 - DILM38
Rated impulse withstand voltage [Uimp]
6000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V AC
Rated operational voltage [Ue]
500 V AC
Safe isolation to EN 61140between coil and auxiliary contacts
400 V AC
Safe isolation to EN 61140between the auxiliary contacts
400 V AC
Rated operational currentConventional free air thermal current, 1 poleat 60 °C [Ith]
16 A
Rated operational currentAC-15220 V 230 V 240 V [Ie]
4 A
Rated operational currentAC-15380 V 400 V 415 V [Ie]
4 A
Rated operational currentAC-15500 V [Ie]
1.5 A
Rated operational currentDC current
Switch-on and switch-off conditions based on DC-13, time constant as specified.
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:1 [24 V]
10 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:1 [60 V]
6 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:1 [110 V]
3 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:1 [220 V]
1 A
Rated operational currentDC currentDC-13 (6xP)24 V [Ie ]
2.5 A
Rated operational currentDC currentDC-13 (6xP)60 V [Ie ]
1 A
Rated operational currentDC currentDC-13 (6xP)110 V [Ie ]
0.5 A
Rated operational currentDC currentDC-13 (6xP)220 V [Ie ]
0.25 A
Rated operational currentControl circuit reliability [Failure rate]
<10-8, < one failure at 100 million operations
(at Ue = 24 V DC, Umin = 17 V, Imin = 5.4 mA) λ
Short-circuit rating without weldingShort-circuit protection maximum fuse500 V
10 A gG/gL
Current heat loss at IthAC operated
2.6 W
Current heat loss at IthDC operated
2.6 W
Current heat loss at IthCurrent heat loss per auxiliary circuit at Ie (AC-15/230 V)
0.16 CO
Rating data for approved types
Auxiliary contactsPilot DutyAC operated
A600
Auxiliary contactsPilot DutyDC operated
P300
Auxiliary contactsGeneral UseAC
600 V
Auxiliary contactsGeneral UseAC
10 A
Auxiliary contactsGeneral UseDC
250 V
Auxiliary contactsGeneral UseDC
1 A