Input data
AC operation
Network type Star network
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Switch-on voltage > 75 V AC
Shut-down voltage < 70 V AC
Electric strength, max. 300 V AC 15 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
Inrush current ≤ 25 A (typical)
Inrush current integral (I2t) < 0.5 A2s
Inrush current limitation typ. 25 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz ±10 %
Mains buffering time typ. 15 ms (120 V AC)
typ. 20 ms (230 V AC)
Current consumption 3.1 A (100 V AC)
2.4 A (120 V AC)
1.3 A (230 V AC)
1.4 A (240 V AC)
Nominal power consumption 285 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.93
Typical response time < 1 s
Input fuse 6.3 A (internal (device protection))
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
POWER factor > 0.9 (120 V AC)
> 0.9 (230 V AC)
DC operation
Nominal input voltage range 110 V DC ... 250 V DC
Input voltage range 110 V DC ... 250 V DC -10 % ... +10 %
Switch-on voltage ≥ 95 V DC
Shut-down voltage < 70 V DC
Voltage type of supply voltage AC/DC
Mains buffering time > 15 ms (230 V AC)
Current consumption 2.5 A (110 V DC)
1.1 A (250 V DC)

Output data
Efficiency > 91 % (for 230 V AC and nominal values)
Output characteristic U/I with dynamic load reserve
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 24 V DC ... 28 V DC (constant capacity)
Nominal output current (IN) 10 A
Dynamic Boost (IDyn.Boost) 15 A (5 s)
Derating > 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 10 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 240 W
360 W
Maximum no-load power dissipation < 5.1 W (230 V)
Power loss nominal load max. < 25 W
Rise time ≤ 12 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK
Maximum switching voltage 30 V AC/DC
Continuous load current 100 mA

Connection data
Input
Connection method Push-in connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm
Output
Connection method Push-in connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 8 mm
Signal
Connection method Push-in connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm

Signaling
Types of signaling LED
Floating signal contact
Signal output: LED status indicator
Signalization designation DC OK
Status display LED
Color green
DC OK UOUT > 0.9 x UN

Electrical properties
Number of phases 1.00
Insulation voltage input/output 3 kV AC (type test)
1.5 kV AC (routine test)

Product properties
Product type Power supply
Product family TRIO POWER
MTBF (IEC 61709, SN 29500) > 1800000 h (25 °C)
> 1000000 h (40 °C)
> 480000 h (60 °C)
Insulation characteristics
Protection class I (in closed control cabinet)
Degree of pollution 2

Dimensions
Width 42 mm
Height 130 mm
Depth 160 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm

Mounting
Mounting type DIN rail mounting
Assembly instructions alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715
With protective coating No

Material specifications
Flammability rating according to UL 94 (housing / terminal blocks) V0
Housing material Metal
Type of housing Aluminum (AlMg3)
Hood version Polycarbonate

Environmental and real-life conditions
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (start-up type tested) -25 °C
Maximum altitude ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 4g, 90 min.
DNV GL CG-0339 / Class B
2 Hz - 100 Hz resonance search, 90 min. in resonance,
2 Hz - 25 Hz, ±1.6 mm amplitude,
25 Hz - 100 Hz, 4g acceleration

Standards and regulations
Rail applications EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety IEC 62368-1 (SELV)
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)

Approvals
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Conformity/Approvals
SIL in accordance with IEC 61508 0

EMC data
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 55011 (EN 55022)
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 6 kV (Test Level 4)
Discharge in air 8 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 3 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 1 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Input/Output asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Commercial data
Item number 2903149
Packing unit 1 pc
Minimum order quantity 1 pc
Sales key CMP
Product key CMPO13
Catalog page Page 256 (C-4-2019)
GTIN 4046356960854
Weight per piece (including packing) 1,122.7 g
Weight per piece (excluding packing) 919 g
Customs tariff number 85044083
Country of origin CN
2903149

Politica de retur

 Puteți returna majoritatea articolelor noi, nedeschise în termen de 14 de zile de la livrare, pentru o rambursare completă. Vom plăti, de asemenea, costurile de transport pentru retur dacă returnarea este rezultatul unei erori noastre (ați primit un articol incorect sau defect etc.).

 Ar trebui să vă așteptați să primiți rambursarea în termen de doua săptămâni de la livrarea pachetului expeditorului returnat, cu toate acestea, în multe cazuri, veți primi o rambursare mai rapid. Această perioadă de timp include timpul de tranzit pentru a primi returnarea dvs. de la expeditor (5 până la 10 zile lucrătoare), timpul necesar pentru procesarea returnării dvs. după ce îl primim (3 până la 5 zile lucrătoare) și timpul necesar banca dvs. pentru a procesa cererea noastră de rambursare (5 până la 10 zile lucrătoare).

 Dacă trebuie să returnați un articol, pur și simplu conectați-vă la contul dvs., vizualizați comanda utilizând link-ul „Finalizare comenzi” din meniul Contul meu și faceți clic pe butonul Returnați articolele. Vă vom anunța prin e-mail cu privire la rambursarea dvs. după ce am primit și procesat articolul returnat.

 

Transport

 

Putem livra practic prin curier la orice adresa din Romania. Rețineți că există restricții pentru unele produse, iar unele produse nu pot fi expediate către destinații internaționale.

 Când plasați o comandă, vom estima datele de expediere și livrare pentru dvs. în funcție de disponibilitatea articolelor dvs. și de opțiunile de livrare pe care le alegeți. În funcție de furnizorul de transport pe care îl alegeți, este posibil ca estimările datei de expediere să apară pe pagina de oferte de livrare.

chat Comentarii (0)